AAAC Conductor( All Aluminium Alloy Conductor)

Details

AAAC Conductor( All Aluminium Alloy Conductor)

 

Application:

Used for overhead distribution and transmission lines especially adjacent to ocean coastlines for corrosion resistance.

 

Standard:

IEC61089,ASTM B-399,BS3242,NFC34125

 

Construction:

AA-6101 aluminum alloy, Concentrically strandedMax. Size 2500MCM, Max. str. No. 91Wires

 

Main Features:

● High strength to weight ratio

● Better sag characteristics

● Improved electrical properties

● Excellent resistance to corrosion

 

AAAC Conductor Data Sheet:

TABLE1-Product Data Sheet-AAAC-IEC61089

Cross-section Area Stranding No. & Wire No.s Approx. Overall Dia. Approx. Weight Rated strength Max. D.C. resistance at 20℃
mm2 No.s mm mm Kg/km kN Ω/km
18.4 7 1.83 5.49 50.4 5.43 1.7896
28.8 7 2.29 6.87 78.7 8.49 1.1453
46.0 7 2.89 8.67 125.9 13.58 0.7158
72.5 7 3.36 10.08 198.3 21.39 0.4545
115.0 19 2.78 13.90 316.3 33.95 0.2877
144.0 19 3.10 15.50 395.4 42.44 0.2302
184.0 19 3.51 17.55 506.1 54.32 0.1798
230.0 19 3.93 19.65 632.7 67.91 0.1439
288.0 19 4.39 21.95 790.8 84.68 0.1151
363.0 37 3.53 24.71 998.9 106.95 0.0916
460.0 37 3.98 27.86 1268.4 135.81 0.0721
518.0 37 4.22 29.54 1426.9 152.79 0.0641
575.0  37 4.45 31.15 1585.5 169. 76 0.0577
645.0 61 3.67 33.03 1778.4 190.14 0.0516
725.0 61 3.89 35.01 2000.7 213.90 0.0458
817.0 61 4.13 37.17 2254.8 241.07 0.0407
921.0 61 4.38 39.42 2540.6 271.62 0.0361
1036.0 91 3.81 41.91 2861.1 305.58 0.0321
1151.0 91 4.01 44.11 3179.0 339.53 0.0289
1289.0 91 4.25 46.75 3560.5 380.27 0.0258
1439.0 91 4.49 49.39 3973.7 424.41 0.0231

 

TABLE2-Product Data Sheet-AAAC-ASTM B399

Code Name Conductor size Stranding No. & Wire No.s Approx. Overall Dia. Approx. Weight Rated strength Max. D.C. resistance at 20℃
AWG (MCM) mm2 No.s mm mm Kg/km Kn Ω/km
Akron   15.51  7 1.68 5.04 43 4.9 2.15980
  4 21.14 7 1.96 5.88 58 6.7 1.35570
Alton 48.69(4) 24.67 7 2.12 6.36 68 7.8 1.58600
  2 33.65 7 2.47 7.41 92 10.7 0.99870
Ames 77.47(2) 39.26 7 2.67 8.01 108 12.5 0.85470
  1/0 53.49 7 3.12 9.36 148 17 0.62590
Azusa 123.3(1/0) 62.46 7 3.37 10.11 172 19.8 0.53650
  2/0 67.45 7 3.5 10.5 186 20.5 0.49740
Anaheim 155.4(2/0) 78.75 7 3.78 11.34 217 24 0.42640
  3/0 85.00 7 3.93 11.79 234 25.9 0.39450
Amherst 195.7 (3/0) 99.20 7 4.25 12.75 274 30.2 0.33730
  4/0 107.20 7 4.42 13.26 296 32.7 0.31190
Alliance 246.9 (4/0) 125.10 7 4.77 14.31 345 38.1 0.26780
  250.0 126.70 19 2.91 14.55 348 39 0.26510
  300.0 152.10 19 3.19 15.95 419 46.8 0.22060
Butte 312.8 158.50 19 3.26 16.3 437 48.8 0.21120
  350.0 177.30 19 3.45 17.25 490 52.3 0.18860
Canton 394.5 199.00 19 3.66 18.3 551 59 0.16760
    202.70 19 3.69 18.45 560 59.8 0.16490
  450.0 228.00 19 3.91 19.55 629 67.2 0.14680
Cairo 456.4 235.80 19 3.98 19.9 652 69.6 0.14310
  500.0 253.40 19 4.12 20.6 698 74.6 0.13220
  550.0 278.70 37 3.1 21.7 770 83.8 0.12000
Darien 559.5 283.50 19 4.36 21.8 782 83.5 0.11810
  660.0 304.00 37 3.23 22.61 836 91.4 0.11050
  650.0 329.40 37 3.37 23.59 910 99 0.10150
Elgin 652.4 330.60 19 4.71 23.55 913 97.4 0.10120
  700.0 354.50 37 3.49 24.43 976 101.9 0.09464
Flint 740.8 375.40 37 3.59 25.13 1033 107.9 0.08944
  750.0 380.20 37 3.62 25.34 1050 109.9 0.08796
  800.0 405.40 37 3.73 26.11 1115 116.9 0.08285
  900.0 456.30 37 3.96 27.72 1256 131.9 0.07351
Greeley 927.2 469.80 37 4.02 28.14 1295 135.9 0.07133
  1000.0 506.70 37 4.18 29.26 1400 145.9 0.06597
  1077.4 483.40 61 3.38 30.42 1509 155.9 0.06120
  1165.1 523.70 61 3.51 31.59 1627 168.9 0.05675
  1250.0 633.30 61 3.63 32.67 1741 179.9 0.05306
  1259.6 564.00 61 3.65 32.85 1760 181.9 0.05248
  1348.8 604.20 61 3.78 34.02 1887 194.9 0.04893
  1439.2 644.50 61 3.9 35.1 2009 207.8 0.04597
  1500.0 760.00 61 3.98 35.82 2092 216.8 0.04414
  1750.0 886.70 61 4.3 38.7 2442 252.8 0.03781

 

TABLE3-Product Data Sheet-AAAC-BS3242

Code Name Nominal Cross-section Area Calculated Cross-section Area Stranding No. & Wire No.s Approx. Overall Dia. Approx. Weight Rated Strength D.C. Resistance at 20°C
mm2 mm2 No.s mm mm Kg/km Kn Ω/km
Box 15         18.82 7 1.85 5.55 52 5.3 1.74950
Acacia 20 23.79 7 2.08 6.24 66 6.7 1.38400
Almond 25 30.10 7 2.34 7.02 83 8.4 1.09340
Cedar 30 35.47 7 2.54 7.62 98 9.9 0.92810
  35 42.18 7 2.77 8.31 116 11.8 0.78040
Fir 40 47.84 7 2.95 8.85 132 13.4 0.68800
Hazel 50 59.87 7 3.3 9.90 165 16.8 0.54980
Pine 60 71.65 7 3.61 10.83 198 20.1 0.45940
  70 84.05 7 3.91 11.73 232 23.5 0.39170
Willow 75 89.73 7 4.04 12.12 247 25.1 0.36690
  80 96.52 7 4.19 12.57 266 27 0.34410
  90 108.00 7 4.44 13.32 299 30.5 0.30230
Oak 100 118.90 7 4.65 13.95 328 33.3 0.27690
  100 118.70 19 2.82 14.10 327 33.3 0.27870
Mulberry 125 150. 90 19 3.18 15.90 416 42.3 0.21920
Ash 150 180.70 19 3.48 17.40 498 50.6 0.18310
Elm 175 211.00 19 3.76 18.80 582 59.1 0.15680
Poplar 200 239.40 37 2.87 20.09 660 86.6 0.13850
  225 270.30 37 3.05 21.35 745 75.7 0.12270
Sycamore 250 303.20 37 3.22 22.54 831 84.9 0.10930
Upas 300 362.10 37 3.53 24.71 998 101.4 0.09156
Walnut 350 421.80 37 3.81 26.67 1163 118.1 0.07860
Yew 400 479.00 37 4.06 28.42 1321 134.1 0.06921
Totara 425 498.10 37 4.14 28.98 1373 139.5 0.06656
Rub us 500 586.90 61 3.5 31.50 1618 164.4 0.05662
Araucaria 700 821.10 61 4.14 37.26 2264 229.8 0.04047

 

TABLE4-Product Data Sheet-AAAC-NFC34125

Code Cross-section Area Stranding No Single wire dia. Approx. overall dia. Approx. weight Rated tensile strength
mm2 No.s mm mm kg/km KN
25 24.2 7 2.10 6.30 66 7.87
35 34.4 7 2.50 7.50 94 11.18
55 54.6 7 3.15 9.45 149 17.75
95 93.3 19 2.50 12.50 254 30.32
153 152.8 19 3.20 16.00 417 49.66
210 210.3 37 2.69 18.83 573 68.35
228 227.8 37 2.80 19.60 621 74.04
248 247.8 37 2.92 20.44 676 80.54
297 297.6 37 3.20 22.40 811 96.72
323 312.6 37 3.28 22.96 853 101.60
366 366.2 37 3.55 31.95 999 119.02
446 445.7 61 3.05 27.45 1215 144.85
475 475.4 61 3.15 28.35 1296 154.51
570 570.2 61 3.45 31.05 1555 185.32
621 620.9 61 3.60 32.40 1693 201.79
926 926.3 91 3.60 32.40 2526 301.05

 

 