products
N2XSY Medium Voltage Single Core Copper Cable (CU/XLPE/CWS/PVC)
Details

Construction

1)Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
2)Conductor screen: Non-metallic, semi-conducting compound
3)Insulation: Cross-linked polyethylene XLPE
4)Insulation screen: Non-metallic, semi-conducting compound
5)Metallic screen: copper wire and tape
6)Binder tape: Non-hygroscopic material

7)Outer sheath: Polyvinyl chloride PVC


Specifications

IEC 60228 Conductors
IEC 60502-2 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 2: Cables for rated voltages of 6 kV(Um=7.2kV) and 30 kV(Um=36kV)


Parameters

Single Core Cable - 6/10kV and 8.7/15kV

No. of cores and nominal cross sectionThickness of insulationCross section of screenThickness of sheathApprox. overall diameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm2)(mm)(mm)(kg/km)(Ω/km)In air(A)In ground(A)
YJSV (N2XSY) - 6/10kV
1x25/163.4161.821.87200.727170155
1x35/163.4161.822.98290.524197187
1x50/163.4161.8249690.387236220
1x70/163.4161.825.711930.268294268
1x95/163.4161.827.214620.193358320
1x120/163.4161.828.717100.153413363
1x150/253.4251.830.220600.124468405
1x185/253.4251.93224500.0991535456
1x240/253.425234.730000.0754631526
1x300/253.4252.136.936000.0601722591
1x400/353.4352.240.245300.047827662
1x500/353.4352.344.155800.0366949744
YJSV (N2XSY) - 8.7/15kV
1x25/164.5161.823.88000.727160180
1x35/164.5161.824.89130.524197188
1x50/164.5161.826.110570.387236221
1x70/164.5161.827.812880.268294271
1x95/164.5161.829.415620.193358232
1x120/164.5161.93118310.153413366
1x150/254.5251.932.521920.124468407
1x185/254.525234.425850.0991535460
1x240/254.5252.136.831620.0754631531
1x300/254.5252.13937520.0601722597
1x400/354.5352.342.447030.047827670
1x500/354.5352.345.357610.0366949745


Single Core Cable - 12/20kV and 18/30kV


No. of cores and nominal cross sectionThickness of insulationCross section of screenThickness of sheathApprox. overall diameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm2)(mm)(mm)(kg/km)(Ω/km)In air(A)In ground(A)
YJSV (N2XSY) - 12/20kV
1x35/165.5161.826.869890.524225150
1x50/165.5161.828.1611360.387270180
1x70/165.5161.930.0613850.268330220
1x95/165.5161.931.6616640.193400265
1x120/165.516233.2619390.153460310
1x150/255.525234.7623040.124520350
1x185/255.5252.136.6627030.0991585400
1x240/255.5252.138.8632700.0754680465
1x300/255.5252.241.2638840.0601775535
1x400/355.5352.344.4648260.047885615
1x500/355.5352.447.5659130.03661000725
YJSV (N2XSY) - 18/30kV
1x35/16816232.212550.524238172
1x50/16816233.414260.387286203
1x70/168162.135.316910.268356246
1x95/168162.137.120030.193434293
1x120/168162.238.622860.153500332
1x150/258252.240.626830.124559366
1x185/258252.342.330960.0991637410
1x240/258252.344.837030.0754745470
1x300/258252.447.243340.0601846524
1x400/358352.550.453290.047938572
1x500/358352.653.364470.03661065725